E 001- CONFORM TO NFPA 70 ( Second Notice) All electrical equipment and wiring shall conform to the requirements of NFPA 70. 210.4a/NFPA 70 Article 620. (*6-7-21- Relay is not mounted to the board but hanging by the wiring.*)(*3-7-22- violation not corrected.*)
MR 029 - TEMPORARY WIRING/BLOCK - Temporary wiring and insulators or blocks in the armatures or poles of magnetically operated switches, contactors, or relays on equipment in service are prohibited per ASME 8.6.1.6.3. Temporary block. Wood stick found on selector.(*6-7-21 - violation is not corrected.*)(*3-7-22*)
MR 021 - ABC FIRE EXTINGUISHER - A properly tested and maintained ABC type fire extinguisher of adequate size shall be provided in the machine rooms, control rooms, and machinery spaces and control spaces per ASME A17.1-8.6.1.6.5. The fire extinguisher in the machine rooms, control rooms, and machinery spaces and control spaces is to be of sufficient size to allow workers within the room to exit safely in the case of a fire within the machine rooms / control rooms occurs during their maintenance procedures. The extinguisher is not meant for usage for returning to the room to fight the fire. The extinguisher is to be located in an area of the room that will allow easy access to the extinguisher by workers. It is recommended that when possible, the extinguisher be located near the jamb side of the elevator room entrance door. ( last inspected 4/2022 ) ( 3/27/25 )
MR 001 - COVERS & PANELS - All missing electrical covers and cabinet panels shall be replaced per NFPA 70-620-4.( cabinet on side of controller missing cover )
P 001 - FREE OF FLUIDS / DEBRIS - Water, oil, and debris shall not be allowed to accumulate on pit floors per ASME A17.1-8.6.4.7.4.(*6-7-21- Debris*)(*3-7-22- violation not corrected.*)
H 002- VISION PANEL ---Shall restore the hoistway door vision panel with laminated or wire glass per ASME A17.1- 2.14.2.5.( FIRST FLOOR ) .(*6-7-21 - violation is not corrected.*)(*3-7-22- violation not corrected.*)
P 009 - LIGHT - A properly guarded and functioning pit light shall be provided per ASME A17.1-2.2.5.(*6-7-21*)(*3-7-22- violation not corrected.*)
CT 009 - CARTOP INSPECTION - The car-top inspection device shall function properly per ASME A17.1-2.26.1.4/8.6.(*3-7-22- Checked inspection device for up and down movement when the car top was accessed at the 6th floor. After running down the hoist way unable to travel back up the hoist way.*)