Elevator Information
106 S MAIN ST
AKRON 44308
1340 FREEPORT RD PITTSBURGH PA15238
EC 028- CAR DOOR RESTRICTORS ---For elevators installed under the 1980 edition of ASME A17.1 and later, means shall be provided to restrict the opening of the car doors outside the landing zone per ASME A17.1- 2.14.5.7
M 006 - BEING REPAIRED - This unit was not in operating condition at the time of the inspection. This unit is required to be inspected once the unit is returned to operational status. The elevator device is subject to continued invoices from our office unless the elevator device is properly removed from service and properly sealed. Please contact our scheduling office to arrange for an inspection at 614-644-2223 or elevators@com.ohio.gov.
MR 032 - CLEAN/REPAIR/REPLACE/ADJUST COMPONENTS - Shall clean, lubricate and adjust applicable components and repair, replace all worn or defective components, and repair or replace damaged or broken parts to prevent the device from becoming unsafe for operation as required by ASME-A17.1- 8.6.2 (Bracket that holds the vale inside the tank is missing).
P 001 - FREE OF FLUIDS / DEBRIS - Water, oil, and debris shall not be allowed to accumulate on pit floors per ASME A17.1-8.6.4.7.4.
T 002 - RELIEF VALVE TEST - Shall perform annual relief valve tests as required per ASME A17.1-8.11 or A18.1 - 10. The completed test form shall be left on- site within the Maintenance Control Program (MCP) or in a location readily available to the inspector. The safety test form will be reviewed during the next on-site state inspection.
MS- OTHER VIOLATIONS ---Other violations. (VISIBLE PARTS OF THE OIL LINE RUNNING FROM MACHINE ROOM TO HOISTWAY, EXHIBITING SURFACE RUST. LEVEL 5. ELEVATOR COMPANY SHALL EVALUATE, DETERMINE CAUSE AND CORRECT.)