Elevator Information

STATE ID
StateId
17458
UNIT STATUS & INSPECTION AGENCY
Status
Active
Inspected By
State of Ohio
LOCATION
Address
CANAL PLACE
540 S MAIN ST
AKRON 44311
OWNER
OwnerAddress
CANAL PLACE LTD
520 S MAIN ST Suite 2517
AKRON OH44311 1010
UNIT INFO
Elevator Type
Passenger
ASME
S01 Ohio Red Book (01/01/1901)-(03/30/1974)
Power Type
ELECTRIC DRUM/TRACT (E)
Capacity (lbs)
5000
Manufacturer Name
OTIS ELEVATOR COMPANY
Speed of Car
300
Total Travel (ft)
30
Total Number of Floor(s) Served
7
Building Name
CANAL PLACE
Local ID
CP101 BLD. 10
SAFETY TEST INFO
Last Load Test
07/18/2024
Last Safety Test
07/18/2024
CERTIFICATE INFO
Expiration Date
03/31/2026
Plan Review Date
03/12/2012
INSPECTION INFO
Last Annual Date
06/29/2018
Last Semi Date
03/28/2025
LAST INSPECTION RESULTS
Date of last Inspection: 03/28/2025
R 001 - FIRE FIGHTERS EMERGENCY OPERATION LOG - All elevators provided with Firefighters Emergency Operation shall be subjected monthly, by authorized personnel, to Phase I recall by use of the key switch, and a minimum of one-floor operation on Phase II. Deficiencies shall be corrected. A record of findings shall be available to elevator personnel and the authority having jurisdiction per ASME A17.1-8.6.11.1.(*6-3-21*)

EC 001 - RESTORE 2-WAY/24 HR - Shall restore 2-way/ 24-hour voice communications (telephone) within the cab enclosure per ASME A17.1-2.27.1.(*3-7-22*)

MR 021 - ABC FIRE EXTINGUISHER - A properly tested and maintained ABC type fire extinguisher of adequate size shall be provided in the machine rooms, control rooms, and machinery spaces and control spaces per ASME A17.1-8.6.1.6.5. The fire extinguisher in the machine rooms, control rooms, and machinery spaces and control spaces is to be of sufficient size to allow workers within the room to exit safely in the case of a fire within the machine rooms / control rooms occurs during their maintenance procedures. The extinguisher is not meant for usage for returning to the room to fight the fire. The extinguisher is to be located in an area of the room that will allow easy access to the extinguisher by workers. It is recommended that when possible, the extinguisher be located near the jamb side of the elevator room entrance door.(*6-7-21- April, 2020*)(*3-7-22- violation not corrected.*) ( 7/10/24 last date checked Apr 2020 )

INSTALLATION INFO
Installer Name
OTIS ELEVATOR COMPANY
Install Date
02/27/1968
PERMIT INFO
Permit Number
5897461
Permit Date
07/05/2018
Permit Type
Alteration/Repair
Scope of Work
NEW CONTROLLER, NEW WIRING, NEW FIXTURES AND CAB INTERIOR UPGRADE