Elevator Information
540 S MAIN ST
AKRON 44311
520 S MAIN ST Suite 2517
AKRON OH44311 1010
R 001 - FIRE FIGHTERS EMERGENCY OPERATION LOG - All elevators provided with Firefighters Emergency Operation shall be subjected monthly, by authorized personnel, to Phase I recall by use of the key switch, and a minimum of one-floor operation on Phase II. Deficiencies shall be corrected. A record of findings shall be available to elevator personnel and the authority having jurisdiction per ASME A17.1-8.6.11.1.(*6-3-21*)
EC 001 - RESTORE 2-WAY/24 HR - Shall restore 2-way/ 24-hour voice communications (telephone) within the cab enclosure per ASME A17.1-2.27.1.(*3-7-22*)
MR 021 - ABC FIRE EXTINGUISHER - A properly tested and maintained ABC type fire extinguisher of adequate size shall be provided in the machine rooms, control rooms, and machinery spaces and control spaces per ASME A17.1-8.6.1.6.5. The fire extinguisher in the machine rooms, control rooms, and machinery spaces and control spaces is to be of sufficient size to allow workers within the room to exit safely in the case of a fire within the machine rooms / control rooms occurs during their maintenance procedures. The extinguisher is not meant for usage for returning to the room to fight the fire. The extinguisher is to be located in an area of the room that will allow easy access to the extinguisher by workers. It is recommended that when possible, the extinguisher be located near the jamb side of the elevator room entrance door.(*6-7-21- April, 2020*)(*3-7-22- violation not corrected.*) ( 7/10/24 last date checked Apr 2020 )